DSE4620 adalah Auto Mains (Utility) Failure Control Module yang telah dikembangkan untuk menyediakan berbagai fitur luar biasa dalam bentuk yang ringkas.
DC SUPPLY
CONTINUOUS VOLTAGE RATING
8 V to 35 V Continuous
CRANKING DROPOUTS
Able to survive 0 V for 50 mS, providing supply was at least 10 V before dropout and supply recovers to 5 V. This is achieved without the need for internal batteries. LEDs and backlight will not be maintained during cranking.
MAXIMUM OPERATING CURRENT
85 mA at 12 V, 96 mA at 24 V
MAXIMUM STANDBY CURRENT
51 mA at 12 V, 47 mA at 24 VMAXIMUM SLEEP CURRENT
35 mA at 12 V, 32 mA at 24 V
MAXIMUM DEEP SLEEP CURRENT
<10 uA at 12 V, <10 uA at 24 VMAINS (UTILITY)
VOLTAGE RANGE
15 V to 415 V AC (Ph-N)
26 V to 719 V AC (Ph - Ph)FREQUENCY RANGE
3.5 Hz to 75 HzOUTPUTS
OUTPUT A (FUEL)
10 A short term, 5 A continuous,
at supply voltage
OUTPUT B (START)
10 A short term, 5 A continuous,
at supply voltage
AUXILIARY OUTPUTs C & D
2 A DC at supply voltage AUXILIARY OUTPUTs E & F
2 A DC at supply voltage GENERATOR
VOLTAGE RANGE
15 V to 415 V AC (Ph-N)
26 V to 719 V (Ph - Ph)FREQUENCY RANGE
3.5 Hz to 75 HzMAGNETIC PICK-UP
VOLTAGE RANGE
+/- 0.5 V to 70 VFREQUENCY RANGE
10,000 Hz (max)
top of page